Rule of thumb is that 10 degrees difference makes reactions go, and things fail, twice as fast. This is not exact science, but ballpark is about right.
Is a chip cooled with water at 45C necessarily going to be hotter than a chip cooled by air? I imagine the temperature differentials between chip and coolant on a water cooled setup are much better than the differential between chip and airflow on a typical air cooled setup.
(Almost) everything chemical, which is at some level almost everything.
Electrical resistance also (generally) increases with temperature, which causes non-linear effects.
(More resistance == more heat, which makes more resistance until the magic smoke comes out, which typically causes a short and resistance drops to zero)
There are some very weird exceptions, but if you don’t know what they are, it won’t help you.
This means that locations where the temperature never comes close to 45C are becoming much more attractive than many of the deserts where many datacenters are being built currently. Not having to pay the CAPEX and OPEX for evaporative cooling is a big difference I imagine.
I have developed water cooled car electronics and there we had to work with 80C coolant with peaks to 105C. And MTBF figures had to be low, so this was a big cost driver for the design.
My city has district heating which covers around 500k people. The peak output of all the heat plants combined is 239 MW, which is around the same heat output as one or two large data centres.
There are no power plants in my city, so to generate the heat there are heat plants which burn natural gas, biomass or (if supplies get low) something similar to bunker fuel.
Of course it's seasonal, but I'm sure the cost of getting rid of the excess heat in summer would outweigh the current costs of the system (it's more expensive per kWh than a gas boiler), as well as the environmental benefits from not burning all this stuff near where people live.
Demand for hot water would be more consistent throughout the year if not for changes to washing machines and detergents that make it possible to do laundry with absurdly cold water (20 degrees) - which I believe is what makes "fast fashion" possible (the stuff would likely melt apart after few rounds in 60 degrees).
District heating is typically a closed loop high pressure system which is not just pute water but has some nasty additives. You then use a heat exchanger in your basement to heat up your hot water coming out of the tap.
Besides, 45C is what needs to go into the data center. What comes out of it is much hotter and you then need to bring it down to 45C. For example by heating your house or your shower water.
Evaporative cooling seems to be some American nonsense.
Here in Europe, the only things using evaporative cooling are large power plants and industrial processes needing to shed a lot of heat. Everything else is either using pure air cooling, cooling based on a nearby river, or in extremely modern/research projects, dump their excess heat into district heating systems [1][2].
For me as a German, reading about Americans complain about water usage for datacenters was a real culture shock.
> Evaporative cooling seems to be some American nonsense.
Don't quote me on that, but I remember OVH proudly advertising their new "passive" DC cooling system, which was based on evaporative cooling. The idea of using less energy, but more water was sold as "green" a few years back.
A lot of the new DC getting out of the ground in China where also designed with evaporative cooling in mind. It's definitely not an "american nonsense".
What is non sensed though is that both China and the U.S are building a lot of their DC designed with evaporative cooling in water stressed region right now.
While it makes sense in terms of cooling (drier air makes evaporative cooling better), I don't think I have to mention the obvious problem of pumping tons of water in dry region.
Some European data centers use evaporative cooling because they got permits long ago, they don't have the physical space for a non-evaporative system, or both. [1] and [2] (both Dutch, because I happened to go there for spring break this year and saw the coverage then) are two examples.
It's not just modern stuff - steel works and other heavy industry used process powered district heating for a very long time. In some cases it created problems when the enterprise went bankrupt or fragmented and suddenly the process that is providing the district heating might no longer be running. :P
This is the dumbest comment line and perpetuates one facet of hate towards datacenter water consumption. Why?
When water evaporates, where does it go?
1. To the void, blinks out of existence to never be seen of again (cool! Violation of conservation of matter/energy)
2. Evaporates into the atmosphere, where it forms as clouds, gaseous water, and condenses to rain
Naturally, the heat is a problem. And running massive fossil fuels is stupid, given we could go all in on solar. But solar also reduces heat effects due to conversion to electricity. Add reflective cooling paint, and we'd be on our way of active cooling electricity generation.
China's doing exactly this. USA? We just open up more closed oil wells, and double down on coal. Smells like, 1800s version of winning with a large dose of cancer.
> 1. To the void, blinks out of existence to never be seen of again (cool! Violation of conservation of matter/energy)
> 2. Evaporates into the atmosphere, where it forms as clouds, gaseous water, and condenses to rain
Problem is, as far as I know, DC do not use rain / river / aquifer water straight up. Water needs to be processed, and processing water is not free. So you use a significant amount of energy to process water who will be just dumped to release heat.
The other thing is, where the water is coming from and where it goes is very important. A lot of DC in China and the U.S right now are being built in drought prone regions. When you evaporate the water, there is no guarantee that it will rain in the same region. So you are draining the aquifer of already water-stressed region, to have it dumped as rain somewhere else that might not have water stress.
Obviously the water isn't destroyed, but the problem is when you pull water out of some deep aquifer. It make take a Very Long Time before that rain can refill the aquifer. Assuming it falls in the right place and not 1000 miles away.
Globally over very long time horizons datacenter water usage is neutral. But over the shorter time periods that we care about, it moves the water around in problematic ways.
Frequently, the water that goes into clouds from some place will not return through rain in the same place.
If you evaporate water in a place where it seldom rains, it is likely that you will make that place drier than it already is, so you should avoid this.
Only for datacenters built in rainy places it does not matter whether they evaporate water.
> 2. Evaporates into the atmosphere, where it forms as clouds, gaseous water, and condenses to rain
The problem is, you can do this on say, a large lake. No big deal there, as long as you can manage fouling. Or you can do this on an ocean if you desalinate the water. There, your assumption holds.
But if your water supply is a small river that already has trouble supplying downstream with enough (clean) water? Suddenly the "lost" water is a real issue for the downstream communities depending on it, either because they have to compensate by digging wells into groundwater aquifers that often have replenishment times measured in years if not decades or centuries, or because they have to deal with riverbeds running dry in the worst case, which places them in an even worse bind given they have to discharge the water from sewage treatment plants in a river that can dilute it enough with fresh water.
Friends don't let friends run evaporative cooling if there is literally any other way.
You make a good point. The current USA push for datacenters is more a game of how much they can externalize the costs to everyone else, and internalize all the gains.
Geothermal is great at heat/cooling control. So is electric condensation of atmospheric water. It's a big energy gathering and controlling problem. And more money can reduce or near eliminate the negatives.
The USA companies are not forced to pay appropriately for current great teach for electricity and cooling. They instead force communities to "deal with it".
And no, data centers do not need drinkable water for the compute. We could have had water cleaning, recycling units, etc. Nope, "too expensive".
> And no, data centers do not need drinkable water for the compute
A bunch of datacentres run on water that is significantly purer than plain old drinking water - they sometimes need a pre-treatment step to purify the incoming utility water. Apparently all those tasty dissolved solids can wreak havoc in a cooling loop...
Well, it killed the chiller for data centers that have liquid cooled racks. Which is good news, 300-350 watts per ton of cooling is better than 1000 watts per ton of cooling from a chiller.
1 ton of cooling = 12,000 BTU/hr = 3.52 kW thermal cooling
Air handlers in every non data center building will continue using chilled water at 45F to 55F (7C to 13C) to maintain a 55F discharge air temp setpoint during cooling.
ASHRAE has a maximum inlet temperature of 45 degrees Celsius. You can order Dell servers configured for this in an air-cooled design. I looked at it for places where proper AC is not readily available or best I could is a fan (mostly industrial facilities with close to no IT).
The Nvidia design is not new, I think here there was a link to a paper a while back discussing the advantages of raising the liquid temperature in liquid-cooled designs.
Now, keep in mind that yes, 45 degrees is quite hot for humans, but if a computer can get to 100 or 150 degrees without cooling, those 45 degrees make the liquid temperature quite cold.
As a parallel, think of the fact that car cooling is done at 90 degrees Celsius. Too hot for humans, but very cool for engines.
No. Similar capex and better opex. Chillers are not very expensive compared to the chips. Data center economics is built around PUE, a ratio of total power / IT power. The optimal data center has PUE=1, a real data center is >1 because some power has to go to facilities and cooling.
Discussion on Nvidia blog post (429 comments) https://news.ycombinator.com/item?id=48660178
I wonder if moving from 30-35 to 45 degrees has an impact on component lifespan
Rule of thumb is that 10 degrees difference makes reactions go, and things fail, twice as fast. This is not exact science, but ballpark is about right.
Is a chip cooled with water at 45C necessarily going to be hotter than a chip cooled by air? I imagine the temperature differentials between chip and coolant on a water cooled setup are much better than the differential between chip and airflow on a typical air cooled setup.
What kind of reactions? What is a typical component that fails do to heat?
(Almost) everything chemical, which is at some level almost everything.
Electrical resistance also (generally) increases with temperature, which causes non-linear effects.
(More resistance == more heat, which makes more resistance until the magic smoke comes out, which typically causes a short and resistance drops to zero)
There are some very weird exceptions, but if you don’t know what they are, it won’t help you.
Electromigration in the wiring on a silicon chip.
So... good for Nvidia's profits?
If the MTBF is still longer than the upgrade cycle, it won’t impact profits.
This means that locations where the temperature never comes close to 45C are becoming much more attractive than many of the deserts where many datacenters are being built currently. Not having to pay the CAPEX and OPEX for evaporative cooling is a big difference I imagine.
I have developed water cooled car electronics and there we had to work with 80C coolant with peaks to 105C. And MTBF figures had to be low, so this was a big cost driver for the design.
power/fiber locations matters far more, that's why we aren't seeing all of the datacenters go to alaska
Also reduces energy use and nukes the water objection.
That's conveniently hot enough for a hot shower. It would be cool to see more district heating/cooling efforts.
In Eastern Europe there's a lot of places that get hot water thru underground pipes from a power plant.
Obviously has downsides though, one time they were renovating and we didn't have hot water for a few weeks.
My city has district heating which covers around 500k people. The peak output of all the heat plants combined is 239 MW, which is around the same heat output as one or two large data centres.
There are no power plants in my city, so to generate the heat there are heat plants which burn natural gas, biomass or (if supplies get low) something similar to bunker fuel.
Of course it's seasonal, but I'm sure the cost of getting rid of the excess heat in summer would outweigh the current costs of the system (it's more expensive per kWh than a gas boiler), as well as the environmental benefits from not burning all this stuff near where people live.
Demand for hot water would be more consistent throughout the year if not for changes to washing machines and detergents that make it possible to do laundry with absurdly cold water (20 degrees) - which I believe is what makes "fast fashion" possible (the stuff would likely melt apart after few rounds in 60 degrees).
Not for distribution, as it needs to be hot enough to kill legionalla.
District heating is typically a closed loop high pressure system which is not just pute water but has some nasty additives. You then use a heat exchanger in your basement to heat up your hot water coming out of the tap.
Besides, 45C is what needs to go into the data center. What comes out of it is much hotter and you then need to bring it down to 45C. For example by heating your house or your shower water.
People do not want to bathe in your unethical cursed water that was used to cool chips creating AI content trained on stolen data!
There was a satire in Germany many years ago where someone sold a filter that would filter out electricity from nuclear power plants.
Business opportunity: sell a device that restores the water's pureness by mining bitcoin into your account.
At least one atom that has passed through your body, also passed through Hitler. You're already tainted.
Datacenters here on Earth will be much less of a problem with less water consumption because they won't need evaporative cooling
Evaporative cooling seems to be some American nonsense.
Here in Europe, the only things using evaporative cooling are large power plants and industrial processes needing to shed a lot of heat. Everything else is either using pure air cooling, cooling based on a nearby river, or in extremely modern/research projects, dump their excess heat into district heating systems [1][2].
For me as a German, reading about Americans complain about water usage for datacenters was a real culture shock.
[1] https://www.br.de/nachrichten/bayern/noch-haeufig-ungenutzte...
[2] https://www.bayern-innovativ.de/emagazin/detail/tu-muenchen-...
> Evaporative cooling seems to be some American nonsense.
Don't quote me on that, but I remember OVH proudly advertising their new "passive" DC cooling system, which was based on evaporative cooling. The idea of using less energy, but more water was sold as "green" a few years back.
A lot of the new DC getting out of the ground in China where also designed with evaporative cooling in mind. It's definitely not an "american nonsense". What is non sensed though is that both China and the U.S are building a lot of their DC designed with evaporative cooling in water stressed region right now. While it makes sense in terms of cooling (drier air makes evaporative cooling better), I don't think I have to mention the obvious problem of pumping tons of water in dry region.
Some European data centers use evaporative cooling because they got permits long ago, they don't have the physical space for a non-evaporative system, or both. [1] and [2] (both Dutch, because I happened to go there for spring break this year and saw the coverage then) are two examples.
[1]- https://www.techzine.nl/nieuws/infrastructure/577227/datacen... [2]- https://www.nrc.nl/nieuws/2026/08/16/nieuw-amerikaans-datace...
It's not just modern stuff - steel works and other heavy industry used process powered district heating for a very long time. In some cases it created problems when the enterprise went bankrupt or fragmented and suddenly the process that is providing the district heating might no longer be running. :P
This is the dumbest comment line and perpetuates one facet of hate towards datacenter water consumption. Why?
When water evaporates, where does it go?
1. To the void, blinks out of existence to never be seen of again (cool! Violation of conservation of matter/energy)
2. Evaporates into the atmosphere, where it forms as clouds, gaseous water, and condenses to rain
Naturally, the heat is a problem. And running massive fossil fuels is stupid, given we could go all in on solar. But solar also reduces heat effects due to conversion to electricity. Add reflective cooling paint, and we'd be on our way of active cooling electricity generation.
China's doing exactly this. USA? We just open up more closed oil wells, and double down on coal. Smells like, 1800s version of winning with a large dose of cancer.
> When water evaporates, where does it go?
> 1. To the void, blinks out of existence to never be seen of again (cool! Violation of conservation of matter/energy)
> 2. Evaporates into the atmosphere, where it forms as clouds, gaseous water, and condenses to rain
Problem is, as far as I know, DC do not use rain / river / aquifer water straight up. Water needs to be processed, and processing water is not free. So you use a significant amount of energy to process water who will be just dumped to release heat.
The other thing is, where the water is coming from and where it goes is very important. A lot of DC in China and the U.S right now are being built in drought prone regions. When you evaporate the water, there is no guarantee that it will rain in the same region. So you are draining the aquifer of already water-stressed region, to have it dumped as rain somewhere else that might not have water stress.
Obviously the water isn't destroyed, but the problem is when you pull water out of some deep aquifer. It make take a Very Long Time before that rain can refill the aquifer. Assuming it falls in the right place and not 1000 miles away.
Globally over very long time horizons datacenter water usage is neutral. But over the shorter time periods that we care about, it moves the water around in problematic ways.
Frequently, the water that goes into clouds from some place will not return through rain in the same place.
If you evaporate water in a place where it seldom rains, it is likely that you will make that place drier than it already is, so you should avoid this.
Only for datacenters built in rainy places it does not matter whether they evaporate water.
> 2. Evaporates into the atmosphere, where it forms as clouds, gaseous water, and condenses to rain
The problem is, you can do this on say, a large lake. No big deal there, as long as you can manage fouling. Or you can do this on an ocean if you desalinate the water. There, your assumption holds.
But if your water supply is a small river that already has trouble supplying downstream with enough (clean) water? Suddenly the "lost" water is a real issue for the downstream communities depending on it, either because they have to compensate by digging wells into groundwater aquifers that often have replenishment times measured in years if not decades or centuries, or because they have to deal with riverbeds running dry in the worst case, which places them in an even worse bind given they have to discharge the water from sewage treatment plants in a river that can dilute it enough with fresh water.
Friends don't let friends run evaporative cooling if there is literally any other way.
You make a good point. The current USA push for datacenters is more a game of how much they can externalize the costs to everyone else, and internalize all the gains.
Geothermal is great at heat/cooling control. So is electric condensation of atmospheric water. It's a big energy gathering and controlling problem. And more money can reduce or near eliminate the negatives.
The USA companies are not forced to pay appropriately for current great teach for electricity and cooling. They instead force communities to "deal with it".
And no, data centers do not need drinkable water for the compute. We could have had water cleaning, recycling units, etc. Nope, "too expensive".
> And no, data centers do not need drinkable water for the compute
A bunch of datacentres run on water that is significantly purer than plain old drinking water - they sometimes need a pre-treatment step to purify the incoming utility water. Apparently all those tasty dissolved solids can wreak havoc in a cooling loop...
Well, it killed the chiller for data centers that have liquid cooled racks. Which is good news, 300-350 watts per ton of cooling is better than 1000 watts per ton of cooling from a chiller.
1 ton of cooling = 12,000 BTU/hr = 3.52 kW thermal cooling
Air handlers in every non data center building will continue using chilled water at 45F to 55F (7C to 13C) to maintain a 55F discharge air temp setpoint during cooling.
https://mitchellt.com/2018/10/23/why-is-55-so-important.html
The same set of companies that make chillers are the ones that make dry coolers: Carrier, Daikin, Trane, York (JCI), Liebert (Vertiv)
I know it is irrational but factual documentaries like the matrix do make me think if we should optimize machines to need body temperature fluids.
We haven't noticed it because we've literally been doing this for decades in non-data-center applications. Holy marketing batmans.
ASHRAE has a maximum inlet temperature of 45 degrees Celsius. You can order Dell servers configured for this in an air-cooled design. I looked at it for places where proper AC is not readily available or best I could is a fan (mostly industrial facilities with close to no IT).
The Nvidia design is not new, I think here there was a link to a paper a while back discussing the advantages of raising the liquid temperature in liquid-cooled designs.
Now, keep in mind that yes, 45 degrees is quite hot for humans, but if a computer can get to 100 or 150 degrees without cooling, those 45 degrees make the liquid temperature quite cold.
As a parallel, think of the fact that car cooling is done at 90 degrees Celsius. Too hot for humans, but very cool for engines.
Sooooo... downsize everything, still run chillers and have better capex for the same-ish opex?
There's no inherent reason this has to be a hard cut or that a hard cut to a different cooling architecture will be the right way to go.
No. Similar capex and better opex. Chillers are not very expensive compared to the chips. Data center economics is built around PUE, a ratio of total power / IT power. The optimal data center has PUE=1, a real data center is >1 because some power has to go to facilities and cooling.
Sure, it expands to space of workable trade offs. Some times that will mean no chillers.